Mini Purge Ejector
Product List
Save time and money on your next abandonment project!
Ability to purge over 4000' of 8" diameter main in about 11 minutes*
No need for expensive & slow moving CO
2
or N slug.
Purge main with your existing air compressor.
2" x 4' Aluminum
extender vent
Summary Procedure:
Isolate and vent section of main to be abandoned in line with operational procedures
Fit Mini Purge to main using ALH System-1 machine.
Provide adequate air inlet vent to other end of main
Attach compressor to airline connector – valve closed
Start compressor
Open air inlet vent/s and open valve on compressor
Open compressed air inlet valve on Mini Purge to introduce compressed air
Continue purge until 10% LEL or less is measured at test point on ejector
Stop operation and remove Mini Purge from main.
Size
Height
Width
Weight
Power
Used on:
2" NPT
4.0'
15"
17.85 lbs
100 psi
3-12" mains