Mini Purge Ejector

Product List
Save time and money on your next abandonment project!

Ability to purge over 4000' of 8" diameter main in about 11 minutes*

No need for expensive & slow moving CO2 or N slug.

Purge main with your existing air compressor.
Mini Purge Ejector Mini Purge Ejector
2" x 4' Aluminum
extender vent


Summary Procedure:


  • Isolate and vent section of main to be abandoned in line with operational procedures


  • Fit Mini Purge to main using ALH System-1 machine.


  • Provide adequate air inlet vent to other end of main


  • Attach compressor to airline connector – valve closed


  • Start compressor


  • Open air inlet vent/s and open valve on compressor


  • Open compressed air inlet valve on Mini Purge to introduce compressed air


  • Continue purge until 10% LEL or less is measured at test point on ejector


  • Stop operation and remove Mini Purge from main.
Size Height Width Weight Power Used on:
2" NPT 4.0' 15" 17.85 lbs 100 psi 3-12" mains